Energy requirements in BR18 — U-values and energy frame

What outer walls, roof and windows should perform

2026-06-16·7 min reading

U-value ≤ 0.30 for external walls, ≤ 0.20 for roofs and ground floors, energy frame 30 kWh/m²/year for dwellings — the concrete BR18 figures the carpenter needs to know, and how to calculate them.

Introduction

The climate envelope — exterior walls, roof/ceiling, windows and terrain deck — is the carpenter's domain. BR18 Chapter 11 sets the minimum U-values allowed in new construction and an energy frame that limits total heating demand.

U-value requirements (new construction)

Building partMinimum requirements (new construction)Indicative tightening (renovation)
Exterior wallU ≤ 0,30 W/m²KU ≤ 0,18 W/m²K
Ceiling/roof against unheated roomU ≤ 0,20 W/m²KU ≤ 0,12 W/m²K
Ground deck against earthU ≤ 0,20 W/m²KU ≤ 0,10 W/m²K
Windows and exterior doorsU ≤ 1,80 W/m²KU ≤ 1,40 W/m²K

Source: BR18 §§ 250–298, verified via bygningsreglementet.dk.

The U-value formula

Eksempel: let træskeletvæg (udefra ind): 22 mm facadebræt (λ = 0,12), 9 mm vindspærreplade (λ = 0,14), 195 mm mineraluldsisolering (λ = 0,036), 12,5 mm gips (λ = 0,22). R_total = 0,04 + 22/120 + 9/140 + 195/36 + 12,5/220 + 0,13 = 0,04 + 0,18 + 0,06 + 5,42 + 0,06 + 0,13 ≈ 5,89 m²K/W → U ≈ 0,17 W/m²K. Langt under de 0,30, og nær renoveringsskærpelsen.

udeinsidefacadebræt22 mmvindspærre9 mmmineraluld195 mmgips12.5 mmR_seR_siheat lossU = 1 / R_total ≈ 0,17 W/m²K
Fig. Cut through the wood frame wall from the outside in — layers proportional to thickness; mineral wool carries R_total