Choosing the RCD type

Type AC, A, F or B — how to make the right choice

The RCD type determines which forms of residual current the device can detect. If you choose wrongly, smooth DC fault currents can «blind» the device so that it does not trip in the event of a fault. This guide takes you through the choice step by step.

  1. Rule out type AC straight away

    Type AC only detects pure sinusoidal AC fault current. It is not permitted in dwellings and is explicitly prohibited for charging points. Do not use it in new installations — always start at type A as a minimum.

    Type ACprohibited in homes + charging points
  2. Choose type A as the starting point

    Type A detects sinusoidal AND pulsating DC fault current and is the standard choice in homes and commercial premises. New dwellings must have at least 2 RCDs of type A with max. 30 mA rated residual operating current.

    New homesmin. 2 × type A, 30 mA
  3. Consider type F with frequency converters

    Type F covers type A's fault types plus certain mixed frequencies from single-phase frequency converters (e.g. modern washing machines and heat pumps). Choose it where the equipment manufacturer recommends at least type F.

  4. Choose the charging point based on DC blocking

    For a charging point, the choice depends on whether the charging unit has an approved, integrated DC fault-current detection (RDC-DD ≤ 6 mA DC per IEC 62955). Always obtain manufacturer documentation confirming this.

    RDC-DD≤ 6 mA DC (approved blocking)
  5. Choose type A OR type B for the charging point

    If the charging unit has approved DC blocking, type A (or type F/A-EV) is sufficient. If it does NOT have approved DC blocking, type B is required — it also detects smooth DC fault current up to 1000 Hz. Type A alone is then insufficient, whatever industry practice says.

    Without DC detectiontype B required

    Type B is more expensive (guideline ~1,500–3,000 kr. each, vat.dk), but is a legal requirement without approved DC detection.

  6. Determine rated tripping current and leakage current limit

    For personal protection, I_ΔN is max. 30 mA. To avoid nuisance tripping, the total operating leakage current per RCD group must not exceed 0.3 × I_ΔN — i.e. max. 9 mA on a 30 mA group. Spread the loads over several RCDs if the leakage current becomes too high.

    Max. leakage current0.3 × I_ΔN (9 mA at 30 mA)
  7. Check I_ΔN in a TT system

    In a TT system, the fault current is limited by the resistance of the earth electrode, and the rated residual operating current must satisfy I_ΔN ≤ 50 V / R_A, where R_A is the sum of the resistances of the earth electrode and the PE conductor. Use the RCD calculator for the specific limit.

    TT requirementsI_ΔN ≤ 50 V / R_A

Source

Based on DS/HD 60364-4-41 and DS/HD 60364-7-722 and the trade's article »RCD types and charging points« (elsikkerhed.dk/ladestandere-i-boliger, tekniq.dk).